Applicable Systems
AC500
AC590
ACS580
ACS880
Symptoms
Ground fault detected on drive output.
Possible Causes
- Motor winding short to ground
- Motor cable insulation breakdown
- Drive output ground leak
Troubleshooting Steps
- Step 1: Megger test motor windings to ground
Insulation > 1 MOhm - Step 2: Inspect motor cable insulation
No ground fault path - Step 3: Disconnect motor and power on drive
Fault clears without load
How to Reset
Reset via control panel after fixing ground fault.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: ABB ACS510/550 User Manual, ABB Drives
Category: PLC & VFD