Applicable Systems
AC500
AC590
ACS580
ACS880
Symptoms
Short circuit detected on drive output.
Possible Causes
- Motor cable short between phases
- Motor winding short to ground
- Output IGBT module short
Troubleshooting Steps
- Step 1: Disconnect motor cables and power on drive
Fault clears without load - Step 2: Megger test motor and cable
Insulation > 1 MOhm - Step 3: Replace drive if IGBT module is shorted
New drive runs motor normally
How to Reset
Power cycle after fixing the short circuit.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: ABB ACS580 Firmware Manual