APC Smart-UPS Error Code A025

APC UPS Major Alarm

Model: Smart-UPS | Code: A025

Applicable Systems
Symmetra LX

Symptoms

The bypass source voltage is outside the acceptable range. The UPS cannot transfer to bypass.

Possible Causes

  • Utility voltage sag or swell
  • Bypass transformer tap setting incorrect

Troubleshooting Steps

  1. Step 1: Check the bypass source voltage
    Voltage is outside the rated range
  2. Step 2: Wait for the voltage to stabilize or adjust the transformer tap
    Voltage returns to within range

How to Reset

To reset: Restore the bypass voltage to within range, then the UPS can transfer to bypass.

Source: APC Smart-UPS User Manual, Schneider Electric/APC

Category: UPS