Cummins PowerCommand Error Code 33

Cummins Generator Critical Hardware

Model: PowerCommand | Code: 33

Applicable Systems
PowerCommand

Symptoms

Shutdown - Rotor fault. The alternator rotor has a fault and the generator has shut down.

Possible Causes

  • Rotor winding short circuit
  • Rotor diode wheel failure

Troubleshooting Steps

  1. Step 1: Check the rotor winding resistance and insulation
    Winding is shorted or insulation is degraded
  2. Step 2: Replace or rewind the rotor
    New rotor operates normally

How to Reset

To reset: Repair or replace the rotor, then reset the controller.

Source: Cummins Power Generation Control Manual, Cummins Inc.