Danfoss FC-51 Error Code Alarm 29

Danfoss PLC & VFD Minor Drive

Model: FC-51 | Code: Alarm 29

Applicable Systems
FC-30 FC-51 FC-101 FC-202 FC-302

Symptoms

The drive shows a warning (not a trip). The display shows Alarm 29 as a warning, indicating that the heat sink temperature is approaching the trip limit. The drive is still running but may trip if temperature continues to rise.

Possible Causes

  • Ambient temperature in the enclosure is high
  • Drive cooling fan efficiency is degrading
  • Drive operating near full load for extended periods
  • Enclosure ventilation inadequate for the heat load

Troubleshooting Steps

  1. Step 1: Check the enclosure ventilation and ambient temperature
    Ambient temperature is within the drive operating range
  2. Step 2: Verify the drive cooling fan is running and airflow is unobstructed
    Fan is operational and air flows freely through the heatsink
  3. Step 3: Inspect the heatsink for dust buildup
    Heatsink fins are clean
  4. Step 4: Reduce the drive load or improve cooling if the warning persists
    Heat sink temperature stabilizes below the warning threshold

How to Reset

To reset: This is a warning, not a trip. The warning clears automatically when the temperature drops below the warning threshold. Caution: Address the cooling issue promptly to prevent the drive from tripping on Alarm 12 (overtemperature trip).

Frequently Asked Questions

  • Q: What is the difference between a warning and an alarm on Danfoss drives?

    A warning does not trip the drive; it alerts the operator to a condition that may lead to a trip. An alarm (trip) stops the drive. Warnings should be addressed before they escalate to alarms.

  • Q: What temperature triggers the heat sink warning?

    The warning threshold varies by drive model but is typically set 5-10 degrees below the trip threshold. For most Danfoss drives, the warning triggers around 75-80 deg C and the trip at 85-90 deg C heat sink temperature.