Eaton 9395 Error Code F06

Eaton UPS Major Battery

Model: 9395 | Code: F06

Applicable Systems
9395

Symptoms

The Eaton 9395 UPS displays fault code F06 indicating over temperature. The internal temperature of the UPS has exceeded the safe operating limit. The UPS will reduce battery charging or transfer to bypass to reduce internal heat generation.

Possible Causes

  • Ambient room temperature above 40C specification limit
  • Cooling fan failure or airflow obstruction
  • Air filter clogged reducing cooling airflow
  • Inverter component degradation causing excessive heat generation

Troubleshooting Steps

  1. Step 1: Check UPS display for F06 and note internal temperature reading
    F06 displayed with temperature above alarm threshold (typically 45-50C)
  2. Step 2: Verify ambient room temperature is within 0-40C operating range
    Room temperature at or below 40C
  3. Step 3: Inspect cooling fans for operation and check for airflow obstructions
    All fans operational, no obstruction in air path
  4. Step 4: Clean or replace air filters if dirty or clogged
    Filters clean, airflow restored to normal volume

How to Reset

To reset: 1) Reduce temperature to within operating range. 2) Press RESET on UPS control panel. 3) Verify UPS returns to normal operation. Caution: High temperature significantly reduces battery life and component reliability.

Frequently Asked Questions

  • Q: What is the ideal operating temperature for Eaton 9395?

    The ideal ambient temperature is 20-25C. The UPS is rated for 0-40C. Every 8C above 25C approximately halves battery life.

  • Q: How often should I replace the air filters?

    Air filters should be inspected monthly and replaced every 3-6 months depending on environment. Dusty environments may require more frequent replacement.

Source: Eaton 9395 UPS Installation & Operation Manual, Document 164201717 Rev 3 (eaton.com)