Applicable Systems
9395
Symptoms
Short circuit: output short circuit detected.
Possible Causes
- Motor cable short
- Motor winding short
- Output IGBT short
Troubleshooting Steps
- Step 1: Disconnect motor and power on
Fault clears without load - Step 2: Megger test motor and cable
Insulation > 1 MOhm - Step 3: Replace drive if IGBT shorted
New drive runs motor
How to Reset
Reset via control panel after fixing short circuit.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Eaton PowerXL DG1 Troubleshooting Guide, Eaton Corporation