Fuji FRENIC Error Code 039

Fuji PLC & VFD Major Overload

Model: FRENIC | Code: 039

Applicable Systems
FRENIC

Symptoms

The FRENIC reports a motor overload fault. The motor thermal model calculated excessive heating based on current and time, tripping to protect the motor.

Possible Causes

  • Motor load torque exceeds the motor rated capacity
  • Duty cycle exceeding the motor thermal class rating
  • Motor cooling insufficient due to blocked ventilation or fan failure

Troubleshooting Steps

  1. Step 1: Check the motor load and verify it is within the rated capacity
    Load torque is within the motor rating
  2. Step 2: Inspect the motor cooling fan and ventilation for blockage
    Motor cooling is adequate and unobstructed
  3. Step 3: Set the motor rated current parameter to match the nameplate value
    Motor thermal model matches the actual motor

How to Reset

To reset: Allow the motor to cool and resolve the overload, then reset.

Source: Fuji FRENIC-Ace Inverter Manual, Fuji Electric Co.

Category: PLC & VFD