Applicable Systems
R-Series

Symptoms

The pressure transducer reading does not match the mechanical pressure gauge by more than 0.5 bar. The controller flags a sensor drift alarm.

Possible Causes

  • Pressure transducer aging causing output signal drift
  • Electrical noise on the transducer signal cable
  • Mechanical gauge calibration error giving a false reference

Troubleshooting Steps

  1. Step 1: Compare the transducer reading on the controller with a calibrated external pressure gauge
    If the external gauge matches, replace the transducer; if it matches the controller, replace the gauge
  2. Step 2: Inspect the transducer cable for damage, shielding issues, or loose terminals
    Repair or reroute the cable away from motor cables to reduce EMI
  3. Step 3: If the transducer is replaced, verify the new unit matches the 4-20mA or 0-10V output specification
    The controller should display pressure within 0.1 bar of the calibrated gauge after replacement

How to Reset

Reset: The sensor alarm clears automatically once the reading stabilizes within the acceptable tolerance band.

Common Replacement Parts

  • Pressure transducer: 4-20mA, 0-16 bar range (Match OEM part number)
  • Signal cable: Shielded twisted pair, 2-core (Keep separate from power cables)

Frequently Asked Questions

  • Q: How do I know if the transducer or the gauge is wrong?

    Use a third calibrated gauge as reference. The one that agrees with the third gauge is correct.

  • Q: Can I run without the pressure transducer?

    Most controllers have a fallback mode using the pressure switch, but efficiency and control quality are reduced.

Source: Service Manual

Category: Compressor