Applicable Systems
AKD

Symptoms

The AKD reports a phase sequence error. The input power phase sequence does not match the expected rotation direction.

Possible Causes

  • Input power phase sequence is reversed at the drive terminals
  • Motor wiring phase sequence incorrect for the desired rotation
  • Phase sequence changed during maintenance without correction

Troubleshooting Steps

  1. Step 1: Check the input power phase sequence with a phase rotation tester
    Phase sequence is incorrect
  2. Step 2: Swap any two input power leads to correct the sequence
    Phase rotation tester shows correct direction
  3. Step 3: Verify the motor rotation direction after correction
    Motor rotates in the correct direction

How to Reset

To reset: Correct the phase sequence, then reset the fault and restart.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Kollmorgen AKD Drive Manual, Kollmorgen Corporation

Category: PLC & VFD