Miura EX-300 Error Code E-08

Miura Boiler Major System

Model: EX-300 | Code: E-08

Applicable Systems
EX-300

Symptoms

Panel display shows E-08, indicating a high exhaust gas temperature alarm. The exhaust temperature sensor has exceeded the setpoint of 260C (500F), triggering a shutdown to protect the boiler pressure vessel and heat transfer surfaces.

Possible Causes

  • Fouled heat transfer tubes reducing heat absorption from combustion gases
  • Excess combustion air causing high stack temperature and efficiency loss
  • Boiler operating above rated capacity due to demand spikes
  • Feedwater temperature too low, increasing temperature differential across tubes

Troubleshooting Steps

  1. Step 1: Inspect and clean the boiler fire tubes - remove soot and scale buildup
    Use rotary tube cleaner or high-pressure water jet per manufacturer method
  2. Step 2: Perform combustion analysis and adjust air-to-fuel ratio
    O2 in exhaust should be 3-5% for gas firing, CO2 should be 8-9% for gas
  3. Step 3: Verify boiler is not firing above rated input capacity
    Check firing rate control and fuel input against nameplate
  4. Step 4: Check economizer or feedwater heater operation if equipped
    Verify feedwater temperature entering boiler is at design value

How to Reset

To reset E-08: 1) Allow the exhaust temperature to drop below 200C (392F). 2) On the panel, acknowledge the alarm. 3) Press the Reset button. 4) The boiler restarts with normal pre-purge and ignition sequence.

Common Replacement Parts

  • MI-EX-3001: Exhaust temperature thermocouple Type K, Miura EX-300 (Verify calibration against reference thermometer)
  • MI-EX-3005: Tube cleaning brush set, carbon steel (Use correct diameter for tube size)
  • MI-EX-3010: Combustion analyzer service kit (Calibrate analyzer before use per manufacturer)

Frequently Asked Questions

  • Q: How often should boiler tubes be cleaned?

    For gas-fired Miura boilers, inspect and clean tubes every 6 months or when exhaust temperature rises 25C (45F) above the baseline reading established at commissioning. For oil-fired boilers, clean every 3 months.

  • Q: What is the ideal exhaust gas temperature?

    For a properly tuned gas-fired Miura EX-300, exhaust gas temperature should be 150-200C (300-392F) at full load. Temperatures above 230C (446F) indicate fouled tubes or excess combustion air and require attention.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Miura EX Series Boiler Installation and Operation Manual, Form IOM-EX-300

Category: Boiler