Miura EX-300 Error Code E-08

Miura Boiler Major System

Model: EX-300 | Code: E-08

Applicable Systems
EX-300

Symptoms

Panel display shows E-08, indicating a high exhaust gas temperature alarm. The exhaust temperature sensor has exceeded the setpoint of 260C (500F), triggering a shutdown to protect the boiler pressure vessel and heat transfer surfaces.

Possible Causes

  • Fouled heat transfer tubes reducing heat absorption from combustion gases
  • Excess combustion air causing high stack temperature and efficiency loss
  • Boiler operating above rated capacity due to demand spikes
  • Feedwater temperature too low, increasing temperature differential across tubes

Troubleshooting Steps

  1. Step 1: Inspect and clean the boiler fire tubes - remove soot and scale buildup
    Use rotary tube cleaner or high-pressure water jet per manufacturer method
  2. Step 2: Perform combustion analysis and adjust air-to-fuel ratio
    O2 in exhaust should be 3-5% for gas firing, CO2 should be 8-9% for gas
  3. Step 3: Verify boiler is not firing above rated input capacity
    Check firing rate control and fuel input against nameplate
  4. Step 4: Check economizer or feedwater heater operation if equipped
    Verify feedwater temperature entering boiler is at design value

How to Reset

To reset E-08: 1) Allow the exhaust temperature to drop below 200C (392F). 2) On the panel, acknowledge the alarm. 3) Press the Reset button. 4) The boiler restarts with normal pre-purge and ignition sequence.

Common Replacement Parts

  • MI-EX-3001: Exhaust temperature thermocouple Type K, Miura EX-300 (Verify calibration against reference thermometer)
  • MI-EX-3005: Tube cleaning brush set, carbon steel (Use correct diameter for tube size)
  • MI-EX-3010: Combustion analyzer service kit (Calibrate analyzer before use per manufacturer)

Frequently Asked Questions

  • Q: How often should boiler tubes be cleaned?

    For gas-fired Miura boilers, inspect and clean tubes every 6 months or when exhaust temperature rises 25C (45F) above the baseline reading established at commissioning. For oil-fired boilers, clean every 3 months.

  • Q: What is the ideal exhaust gas temperature?

    For a properly tuned gas-fired Miura EX-300, exhaust gas temperature should be 150-200C (300-392F) at full load. Temperatures above 230C (446F) indicate fouled tubes or excess combustion air and require attention.

Source: Miura EX Series Boiler Installation and Operation Manual, Form IOM-EX-300

Category: Boiler