NORD SK Error Code N006

NORD PLC & VFD Major Power

Model: SK | Code: N006

Applicable Systems
SK

Symptoms

The SK reports an input phase loss fault. One of the three input power phases is missing, causing input imbalance.

Possible Causes

  • One input phase fuse blown or breaker tripped
  • Loose input power wire on one phase terminal
  • Transformer or supply phase failure

Troubleshooting Steps

  1. Step 1: Measure all three input phase voltages at the drive terminals
    All three phases have balanced voltage
  2. Step 2: Check the input wiring connections for tightness
    All input connections are tight
  3. Step 3: Replace blown fuses or reset tripped breakers
    All three phases are restored

How to Reset

To reset: Restore all three input phases, then reset the fault.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: NORD SK Drive System Manual, NORD Drives

Category: PLC & VFD