Applicable Systems
ATV320
ATV340
ATV630
ATV930
Symptoms
The drive has detected an internal error related to the CPU. This indicates a fault in the RAM, flash memory, or task execution within the drive's processor.
Possible Causes
- Internal CPU RAM fault
- Flash memory corruption
- Internal task scheduling fault
- Electromagnetic interference affecting CPU operation
Troubleshooting Steps
- Step 1: Turn off all sources of power to the drive (main power and control power)
Drive display goes completely blank - Step 2: Wait at least 10 seconds for all internal capacitors to discharge
Drive is fully powered down - Step 3: Re-apply power to the drive and check if the error clears
Drive powers up normally without INFE error - Step 4: If the error returns, remove control wiring from Logic, Analog, Relay, and Communication terminals one at a time to isolate potential noise sources
Error does not recur when the noise-inducing wiring is removed - Step 5: If the problem persists after isolating wiring, contact Schneider Electric Product Support for drive replacement
Drive is repaired or replaced under warranty
How to Reset
To reset: 1) Turn off ALL power sources. 2) Wait 10+ seconds. 3) Re-apply power. If INFE recurs, isolate control wiring. If still present, the drive needs replacement.
Frequently Asked Questions
- Q: What does INFE mean on ATV320?
Internal CPU error (error 14) - RAM, flash, or task fault. Power cycle the drive (wait 10s). If it returns, isolate control wiring. If still present, contact Schneider support for replacement.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Schneider Electric FAQ FA313057; Schneider ATV320 Programming Manual