Applicable Systems
ATV320
ATV340
ATV630
ATV930
Symptoms
The analog input AI3 configured for 4-20mA has detected a signal loss. The current on AI3 and COM has fallen below 4mA, indicating a broken wire or failed sensor.
Possible Causes
- 4-20mA signal wire on AI3 is disconnected or broken
- Sensor or transmitter providing the 4-20mA signal has failed
- AI3 is configured for 4-20mA but no signal source is connected
- Signal loop resistance is too high causing voltage drop
Troubleshooting Steps
- Step 1: Check the AI3 wiring and ensure the 4-20mA signal source is connected
AI3 wiring is intact and signal source is operational - Step 2: Verify the AI3 parameter configuration matches the signal type (0-5V vs 4-20mA)
AI3 is correctly configured for the actual signal type - Step 3: If AI3 is not needed, deactivate the alarm by setting the alarm group parameter (A1C/A2C/A3C) to 'unassigned'
Alarm is deactivated and drive operates normally - Step 4: If the alarm is needed, check the sensor/transmitter for proper operation
Sensor provides a stable 4-20mA output
How to Reset
To reset: 1) Restore the 4-20mA signal on AI3. 2) Press STOP/RESET. 3) Restart. Alternatively, deactivate AI3 alarm if not needed: CONF->FULL->I/O, set A3C to 'unassigned'.
Frequently Asked Questions
- Q: How do I clear LFF3 on ATV320?
Check AI3 wiring and signal source. If AI3 is not needed, go to CONF->FULL->I/O and set A3C (alarm group 3) to unassigned. If needed, fix the 4-20mA signal.
Source: Schneider Electric FAQ FA313354; Schneider ATV320 Programming Manual
Category: Electrical