Applicable Systems
Okken

Symptoms

The Masterpact MTZ breaker trips on short-circuit with the I indicator active. The Micrologic trip unit logs the fault current magnitude and waveform. The downstream bus is de-energized.

Possible Causes

  • Severe phase-to-phase short circuit in the switchgear bus or cable
  • Faulty connection on the busbar creating high-impedance arc fault
  • Incorrect breaker rating for the prospective short-circuit current
  • Failure of a downstream device causing a bolted fault

Troubleshooting Steps

  1. Step 1: Do not reclose immediately. Visually inspect the switchgear through the inspection window for smoke or damage
    No visible smoke, arcing marks, or deformed busbars are present
  2. Step 2: Megger all outgoing feeders and bus sections at 1000V DC
    All sections read >10 MOhm to ground and between phases
  3. Step 3: Verify the breaker short-circuit rating (Icu) exceeds the calculated prospective fault current at the installation point
    Icu > Isc_max per IEC 60947-2; documentation confirms coordination
  4. Step 4: Open each outgoing breaker sequentially and re-energize to isolate the faulted section
    System remains stable when the faulted feeder is isolated

How to Reset

Reset the Micrologic trip unit by pressing the Test/Reset button after confirming the fault is cleared. Reclose the Masterpact only after verifying all downstream insulation is intact.

Common Replacement Parts

  • LV848260SP: Schneider Masterpact MTZ2 20H1 with Micrologic 7.0X (Verify frame size, breaking capacity, and communication options)

Frequently Asked Questions

  • Q: What does the I trip mean on Micrologic?

    It indicates an instantaneous short-circuit trip. The trip unit detected a current exceeding the instantaneous pick-up (typically 2-15x In).

  • Q: Can I test the Micrologic trip unit without tripping the breaker?

    Yes. Use the built-in Test function which simulates the trip logic without opening the main contacts. Refer to the user manual.