Applicable Systems
Modicon M221 Modicon M241 Modicon M251 Modicon M340 Modicon M580 Altivar

Symptoms

Output phase loss: motor phase missing detected.

Possible Causes

  • Motor winding open circuit
  • Output cable broken
  • Drive output IGBT not switching

Troubleshooting Steps

  1. Step 1: Check output cable continuity
    All phases have continuity
  2. Step 2: Measure motor winding resistance
    All phases balanced
  3. Step 3: Test drive output
    All phases switching

How to Reset

Reset via control panel after fixing output phase.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Schneider Electric ATV320 Programming Manual

Category: PLC & VFD