Applicable Systems
Modicon M221 Modicon M241 Modicon M251 Modicon M340 Modicon M580 Altivar

Symptoms

DC bus voltage exceeded trip threshold.

Possible Causes

Deceleration too fast, regenerative energy too high, or input voltage too high.

Troubleshooting Steps

Extend deceleration time, install brake resistor, check supply voltage.

How to Reset

Fix cause and reset

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Schneider ATV630 fault manual

Category: Electrical