Archive Database Full - Historical Data Logging Stopped

Siemens WinCC SCADA Warning SCADA

Model: Siemens WinCC SCADA | Code: WinCC 700002

Applicable Systems
WinCC

Symptoms

WinCC archive database reached capacity; historical data logging stopped; old data may need archiving/deletion.

Possible Causes

  • Database file at maximum size
  • No automatic data compression configured
  • Database maintenance not performed

Troubleshooting Steps

  1. Step 1: Check archive database size in WinCC Archive Manager
    Size below configured limit
  2. Step 2: Review data retention settings (reduce if needed)
    Retention period appropriate
  3. Step 3: Archive old data to external storage
    Archive completed successfully
  4. Step 4: Configure automatic database compression
    Compression enabled
  5. Step 5: Restart data logging in WinCC
    Logging resumed, no errors

How to Reset

Clear via WinCC Archive Manager after database maintenance.

Frequently Asked Questions

  • Q: How to configure WinCC data retention?

    In WinCC Archive Manager, set retention period per archive variable. Old data is automatically deleted. Typical: 30 days for high-res, 1 year for hourly aggregates.

Source: Siemens WinCC System Manual