Applicable Systems
GA700
GA500
A1000
V1000
J1000
Symptoms
Z-phase noise abnormal detection
Possible Causes
- PG cable noise interference
- PG cable wiring incorrect or broken
- 24+ pole motor at zero speed
- PG option card or motor-side PG damaged
Troubleshooting Steps
- Route PG cable away from drive output lines
- Check PG cable wiring/breaks; ground shield properly
- Set F1-46=1 for mechanical angle detection; adjust F1-17/F1-47 thresholds
- Restart drive; if persists, replace PG card or PG
How to Reset
Reset by: 1) Correct the fault condition. 2) Press RESET button on operator panel. 3) Verify fault does not recur.
Source: Yaskawa GA700 Fault Code Manual (jinxinservice.com)
Category: Electrical