Yaskawa dv3: Reverse rotation detection

Yaskawa Electrical Fault vfd

Model: GA700/A1000 | Code: dv3

Applicable Systems
GA700 GA500 A1000 V1000 J1000

Symptoms

Reverse rotation detection

Possible Causes

  • E5-11 PG origin pulse compensation set improperly
  • PG replaced or motor rotation direction changed
  • Motor driven by external force
  • PG cable noise interference
  • PG cable wiring incorrect or broken
  • F1-05 rotation direction mismatch
  • Magnetic pole position detection failed
  • n8-84 polarity discrimination current too small
  • Initial magnetic pole estimation failed

Troubleshooting Steps

  • Set E5-11 correctly per motor nameplate
  • Perform Z-pulse position self-learning
  • Check motor rotation direction; investigate external force cause
  • Ground PG cable shield
  • Check PG cable wiring/breaks
  • Connect motor U/V/W phases correctly
  • Check U6-57; increase n8-84 if <819
  • Increase n8-84 above factory value
  • For IPM motor: perform high-frequency overlap self-learning
  • Restart; if persists, replace PG card or PG

How to Reset

Reset by: 1) Correct the fault condition. 2) Press RESET button on operator panel. 3) Verify fault does not recur.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Yaskawa GA700 Fault Code Manual (jinxinservice.com)

Category: Electrical