Yaskawa GA700 Error Code GF

Yaskawa PLC & VFD Major Drive

Model: GA700 | Code: GF

Applicable Systems
GA700 GA500 A1000 V1000 J1000

Symptoms

The drive trips. The digital operator displays GF, indicating a ground fault. The drive has detected that leakage current from one or more output phases to ground exceeds the threshold.

Possible Causes

  • Motor cable insulation failure to ground
  • Motor winding insulation failure to ground
  • Moisture or water in the motor or junction box
  • Cable gland or conduit fitting allowing water ingress

Troubleshooting Steps

  1. Step 1: Disconnect the motor cable and megger it to ground
    Cable insulation resistance is in the megohm range
  2. Step 2: Megger the motor windings to ground
    Motor insulation resistance exceeds the minimum requirement
  3. Step 3: Inspect motor junction box and cable glands for moisture or water
    Junction box is dry and properly sealed
  4. Step 4: Replace cables or motors with failed insulation
    System operates without ground faults after replacement

How to Reset

To reset: 1) Fix the insulation failure (replace cable or motor). 2) Press RESET. Caution: Ground faults are safety hazards. Do not reset repeatedly without fixing the root cause. Inspect all motor cables and the motor.

Frequently Asked Questions

  • Q: How does the drive detect a ground fault?

    The drive measures the current in each output phase. If the vector sum of the three-phase currents is not zero, the difference represents ground leakage current. When this exceeds the threshold, the GF fault trips.

  • Q: What insulation resistance is acceptable for a motor?

    For 400V motors, IEEE 43 recommends insulation resistance above 100 megohm. Values below 1 megohm indicate severely degraded insulation that will cause ground faults. Use a 500V megohmmeter for testing.

Source: Yaskawa GA700 Technical Manual, 2023

Category: PLC & VFD