Yaskawa GA700 Error Code POF

Yaskawa PLC & VFD Major System

Model: GA700 | Code: POF

Applicable Systems
GA700 GA500 A1000 V1000 J1000

Symptoms

The drive trips. The digital operator displays POF, indicating a control power loss. The internal control power supply has failed or been interrupted.

Possible Causes

  • Internal control power supply hardware failure
  • Control power circuit component degradation
  • Momentary complete power loss exceeding ride-through capacity
  • Internal fuse or protection device opened

Troubleshooting Steps

  1. Step 1: Check if there was a complete power interruption in the facility
    Confirm with facility operations whether a total power loss occurred
  2. Step 2: Verify the input power is stable and present at the drive terminals
    Input voltage is present and stable
  3. Step 3: Power cycle the drive completely (remove and restore input power)
    Drive powers up normally after a full power cycle
  4. Step 4: If the fault recurs, the internal control power supply needs service
    Drive operates normally after internal service

How to Reset

To reset: 1) Power cycle the drive completely. 2) If the fault recurs, contact Yaskawa service. Caution: POF faults that recur after power cycling indicate internal hardware failure requiring professional service.

Frequently Asked Questions

  • Q: What is the ride-through capability of Yaskawa drives?

    Ride-through is the ability to maintain operation during brief power interruptions. For complete power loss, the drive can typically maintain control for 2-5 seconds using stored energy in the DC bus capacitors. If the interruption exceeds this, POF trips.

  • Q: How do I configure the drive response to power loss?

    Parameters L2-01 through L2-05 configure the drive's response to power loss. Options include coasting to stop, restarting automatically when power returns, or tripping with a fault. Set these according to your application's safety requirements.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Yaskawa GA700 Technical Manual, 2023

Category: PLC & VFD