Yokogawa Centum Error Code Y024

Yokogawa SCADA Major I/O

Model: Centum | Code: Y024

Applicable Systems
Centum

Symptoms

The Centum reports an internal overheat fault. The heatsink temperature exceeded the protection threshold and the drive tripped.

Possible Causes

  • Cooling fan failure or blocked airflow in the Yokogawa enclosure
  • Ambient temperature exceeding the drive rated maximum
  • Drive mounted without adequate clearance for heat dissipation

Troubleshooting Steps

  1. Step 1: Check the cooling fan for operation and replace if not spinning
    Fan runs at full speed after replacement
  2. Step 2: Verify the ambient temperature around the drive is below the rated maximum
    Ambient temperature is within the rated range
  3. Step 3: Ensure the drive has at least 100mm clearance on all sides for airflow
    Airflow is unobstructed around the drive

How to Reset

To reset: Allow the drive to cool, fix the cooling issue, then reset the fault.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Yokogawa Centum VP System Manual, Yokogawa Electric Corporation

Category: SCADA