ABB ACS580 Error Code 3333

ABB PLC & VFD Major Ground Fault

Model: ACS580 | Code: 3333

Applicable Systems
AC500 AC590 ACS580 ACS880

Symptoms

Ground fault detected on drive output.

Possible Causes

  • Motor winding short to ground
  • Motor cable insulation breakdown
  • Drive output stage ground leak

Troubleshooting Steps

  1. Step 1: Disconnect motor cables and power on drive
    Fault clears without load
  2. Step 2: Megger test motor windings to ground
    Insulation > 1 MOhm
  3. Step 3: Inspect motor cable insulation
    No ground leakage path

How to Reset

Reset via control panel after fixing ground fault.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: ABB ACS580 Firmware Manual

Category: PLC & VFD