Allen-Bradley CompactLogix Error Code 16#0011

Allen-Bradley PLC & VFD Minor System

Model: CompactLogix | Code: 16#0011

Applicable Systems
MicroLogix CompactLogix ControlLogix PowerFlex

Symptoms

The controller's OK LED remains green but a minor fault is logged. The battery backup voltage is low, indicating that the battery needs replacement. The controller continues to operate normally.

Possible Causes

  • Battery has reached end of life
  • Battery was not replaced after the low battery warning
  • Battery contact corrosion or loose connection
  • Extended power-off period drained the battery

Troubleshooting Steps

  1. Step 1: Check the minor fault log in Studio 5000 for the battery low warning
    Confirm the fault is a low battery warning (type 16#0011)
  2. Step 2: Power down the controller and locate the battery compartment
    Battery is accessible for replacement
  3. Step 3: Remove the old battery and install a new one of the same type
    New battery is installed with correct polarity
  4. Step 4: Clear the minor fault in Studio 5000
    Battery fault is cleared and no new battery warnings appear

How to Reset

To reset: 1) Replace the controller battery with a new one. 2) Clear the minor fault in Studio 5000 via Controller Properties > Minor Faults. Caution: Replace the battery while the controller is powered to avoid losing volatile memory contents.

Common Replacement Parts

  • 1747-BA: Controller backup battery (Replace with the same catalog number; do not use substitutes)

Frequently Asked Questions

  • Q: How often should I replace the PLC battery?

    Typically every 2-3 years, but follow the manufacturer's recommendation. Replace proactively when the low battery warning first appears.

  • Q: What happens if the battery dies completely?

    The controller will lose its retained memory contents, including timer and counter accumulated values, when power is removed.

Source: Rockwell Automation CompactLogix 5370 User Manual, Publication 1756-UM522