Allen-Bradley CompactLogix Error Code 16#0004

Allen-Bradley PLC & VFD Major Programming

Model: CompactLogix | Code: 16#0004

Applicable Systems
MicroLogix CompactLogix ControlLogix PowerFlex

Symptoms

The OK LED turns red. The controller reports a user program checksum error. The program in the controller memory does not match the expected checksum, indicating corruption.

Possible Causes

  • Memory corruption due to power loss during program download
  • Electrical noise corrupted controller memory
  • Firmware bug caused memory write error
  • Hardware memory failure

Troubleshooting Steps

  1. Step 1: Read the major fault code in Studio 5000
    Confirm the fault is a checksum error (type 16#0004)
  2. Step 2: Attempt to re-download the project to the controller
    Project downloads successfully and checksum matches
  3. Step 3: If re-download fails, perform a firmware re-flash
    Firmware update completes and project can be downloaded
  4. Step 4: If the error persists, replace the controller hardware
    New controller accepts the project without checksum errors

How to Reset

To reset: 1) Clear the major fault in Studio 5000. 2) Re-download the project. 3) If the error persists, re-flash firmware and retry. 4. If hardware is suspected, replace the controller. Caution: Checksum errors may indicate failing memory, so plan for hardware replacement.

Frequently Asked Questions

  • Q: What causes a program checksum error?

    Memory corruption from power loss during downloads, electrical noise, firmware bugs, or hardware memory failure can alter the program and cause a checksum mismatch.

  • Q: Is a checksum error a sign of failing hardware?

    If the error recurs after re-downloading the project and re-flashing firmware, yes. It likely indicates permanent memory degradation in the controller.

Source: Rockwell Automation CompactLogix 5370 User Manual, Publication 1756-UM522

Category: PLC & VFD