Caterpillar EMCP 4.2 Error Code 164-2

Caterpillar Generator Minor Engine

Model: EMCP 4.2 | Code: 164-2

Applicable Systems
EMCP 4.2

Symptoms

The EMCP 4.2 reports fault 164-2 for the Injector Actuation Pressure circuit where the data is erratic, intermittent, or incorrect. This indicates a loose connection or signal noise rather than a hard short.

Possible Causes

  • IAP sensor connector partially disconnected or corroded
  • Signal wire intermittent open circuit due to harness flex
  • Sensor internal element failing intermittently with temperature
  • Ground loop or electrical noise on sensor signal line

Troubleshooting Steps

  1. Step 1: Check EMCP fault log for intermittent 164-2 pattern
    Fault appears and clears intermittently during operation
  2. Step 2: Inspect IAP sensor connector for corrosion, loose pins, or incomplete seating
    Connector clean, fully seated with locking tab engaged
  3. Step 3: Wiggle test the wiring harness from sensor to ECM while monitoring EMCP
    No fault transitions observed during harness manipulation
  4. Step 4: Replace IAP sensor if intermittent fault persists after connector service
    Fault no longer appears after sensor replacement

How to Reset

To reset: 1) Repair the intermittent connection or replace sensor. 2) Press FAULT RESET on EMCP. 3) Press AUTO.

Frequently Asked Questions

  • Q: Why does fault 164-2 come and go?

    FMI 2 faults are typically caused by intermittent connections, vibration-induced opens, or temperature-dependent sensor failures. The signal is sometimes valid, sometimes not.

  • Q: Can weather affect this fault?

    Yes. Temperature changes can cause connector expansion/contraction, and moisture can create intermittent conductivity paths. Seasonal occurrence is common.

Source: Caterpillar EMCP 4.2 Operation & Maintenance Manual (LERMPMM), caterpillarfaultcodes.com CID-FMI Reference

Category: Generator