Caterpillar EMCP 4.2 Error Code 268-3

Caterpillar Generator Major Controller

Model: EMCP 4.2 | Code: 268-3

Applicable Systems
EMCP 4.2

Symptoms

The EMCP 4.2 controller reports a programmed parameter fault. The system voltage on the parameter circuit is above normal or shorted to a high voltage source. The generator set may not start or may shut down depending on the affected parameter.

Possible Causes

  • Parameter programming error or corruption
  • Wiring short between parameter circuit and power source
  • ECM internal fault affecting parameter memory
  • External voltage surge damaging parameter circuit

Troubleshooting Steps

  1. Step 1: Navigate to EMCP DIAGNOSTICS menu and read active fault codes
    Fault code 268-3 displayed as active with timestamp
  2. Step 2: Check parameter settings using Cat ET (Electronic Technician)
    All parameters match factory default values
  3. Step 3: Inspect wiring harness between ECM and parameter sensors for shorts
    No continuity to power source when unplugged at ECM
  4. Step 4: Re-flash ECM with latest parameter file if values are corrupted
    Parameters successfully written and verified

How to Reset

To reset: 1) Correct the parameter fault. 2) Press FAULT RESET on EMCP. 3) Press AUTO. Caution: Never reset without verifying all parameters are correct.

Frequently Asked Questions

  • Q: What does CID 268 represent on Cat EMCP 4.2?

    CID 268 is the Programmed Parameter Fault identifier. It indicates a problem with the programmable parameters stored in the ECM.

  • Q: Can I continue running the generator with fault 268-3 active?

    It depends on the specific parameter affected. Some parameters are non-critical, but voltage-related parameters (FMI 3) should be investigated immediately as they may indicate a short circuit.

Source: Caterpillar EMCP 4.2 Operation & Maintenance Manual (LERMPMM), caterpillarfaultcodes.com CID-FMI Reference

Category: Generator