Caterpillar EMCP 4.2 Error Code C014

Caterpillar Generator Critical Power

Model: EMCP 4.2 | Code: C014

Applicable Systems
EMCP 4.2

Symptoms

The generator set reports a reverse power trip. The generator is absorbing power from the grid.

Possible Causes

  • Generator output insufficient to carry the load
  • Parallel operation synchronization error
  • Engine power loss while paralleled

Troubleshooting Steps

  1. Step 1: Check the generator power output
    Output is positive and delivering load
  2. Step 2: Verify the parallel operation settings
    Synchronization is correct
  3. Step 3: Check the engine power output
    Engine delivers rated power

How to Reset

To reset: Resolve the reverse power condition, then reset the protection.

Source: Caterpillar Generator Set Manual, Caterpillar Inc.

Category: Generator