Cleaver-Brooks CB-700-250 Error Code E2

Cleaver-Brooks Boiler Major System

Model: CB-700-250 | Code: E2

Applicable Systems
Cleaver-Brooks Hawk 6000 Controller

Symptoms

Controller displays E2, indicating a flame failure alarm. The burner management system detected loss of flame signal during the main flame operation period. The burner has shut down and locked out after the retry sequence.

Possible Causes

  • Dirty or misaligned burner nozzle causing poor fuel atomization
  • Faulty flame scanner or flame rod not detecting flame properly
  • Fuel supply pressure dropped below minimum during burner operation
  • Combustion air damper misadjusted or blocked air intake

Troubleshooting Steps

  1. Step 1: Inspect and clean the burner nozzle - verify correct size and spray pattern
    Replace nozzle if worn or if spray pattern is irregular
  2. Step 2: Clean the flame scanner lens or flame rod and verify signal strength
    Scanner should produce at least 20V DC signal when viewing flame
  3. Step 3: Check fuel supply pressure at the burner inlet during operation
    Gas pressure should be within manufacturer specified range for firing rate
  4. Step 4: Inspect combustion air intake and damper for obstructions
    Verify damper opens fully and air filters are clean

How to Reset

To reset E2: 1) Allow the burner management system to complete its post-purge cycle. 2) Press the Reset button on the flame safeguard controller. 3) The burner will attempt a restart through the full purge and ignition sequence. 4) If flame is established and maintained, normal operation resumes.

Common Replacement Parts

  • CB-830-201: Burner nozzle, Cleaver-Brooks CB-700 (Verify gallon per hour rating and spray angle match specification)
  • CB-830-205: Flame scanner UV type, self-checking (Clean lens monthly with lint-free cloth and approved cleaner)
  • CB-830-210: Gas pressure regulator, 2 inch NPT (Verify outlet pressure stability under flow)

Frequently Asked Questions

  • Q: What causes flame failure on a Cleaver-Brooks boiler?

    The most common causes are dirty burner nozzles, faulty flame scanners, and fuel pressure fluctuations. Regular cleaning and calibration of burner components prevents most flame failure events.

  • Q: How many times can I reset the flame safeguard before calling a technician?

    The flame safeguard controller typically allows 1-3 reset attempts. If the burner does not establish and maintain flame after 2 reset attempts, stop resetting and contact a qualified boiler technician to diagnose the root cause.

Source: Cleaver-Brooks CB-700 Boiler Operation and Maintenance Manual, Form 750-250

Category: Boiler