Danfoss FC-101 Error Code Alarm 12

Danfoss PLC & VFD Critical Drive

Model: FC-101 | Code: Alarm 12

Applicable Systems
FC-30 FC-51 FC-101 FC-202 FC-302

Symptoms

The drive trips. The display shows Alarm 12, indicating drive overtemperature. The internal temperature sensor has detected that the drive heatsink temperature exceeds the safe limit.

Possible Causes

  • Drive cooling fan failed or airflow blocked
  • Ambient temperature exceeds drive rating
  • Drive installed in an inadequately ventilated enclosure
  • Drive operating at high duty cycle without sufficient cooling

Troubleshooting Steps

  1. Step 1: Check the drive cooling fan for operation
    Fan is running and airflow is unobstructed
  2. Step 2: Measure the ambient temperature inside the enclosure
    Ambient temperature is within the drive rated range
  3. Step 3: Inspect the drive heatsink for dust or debris blocking airflow
    Heatsink is clean and air can flow freely
  4. Step 4: Improve enclosure ventilation or reduce drive load if ambient is high
    Drive temperature stays within safe limits

How to Reset

To reset: 1) Allow the drive to cool. 2) Fix the cooling issue (replace fan, clean heatsink, improve ventilation). 3) Press RESET. Caution: Repeated overtemperature trips damage drive power components permanently.

Frequently Asked Questions

  • Q: How do I clean a Danfoss drive heatsink?

    Power down the drive and wait for capacitors to discharge. Use low-pressure compressed air (max 3 bar) to blow dust from the heatsink fins. Do not use solvents or liquids.

  • Q: What is the maximum ambient temperature for Danfoss drives?

    Most Danfoss FC series drives are rated for ambient temperatures up to +45 or +50 deg C. Above this, output derating is required. Check the design guide for the specific model.

Source: Danfoss VLT FC-101 Design Guide, 2023