Applicable Systems
FC-30 FC-51 FC-101 FC-202 FC-302

Symptoms

Controller displays E1, indicating the S3 sensor (defrost termination) is open or shorted. The controller cannot execute automatic defrost termination and will fall back to time-based defrost only.

Possible Causes

  • Defrost termination sensor S3 wiring damaged or disconnected
  • Sensor S3 has failed and reads open circuit or short circuit
  • Terminal block corrosion causing intermittent connection
  • Electrical noise or moisture in the sensor conduit

Troubleshooting Steps

  1. Step 1: Check the S3 sensor wiring at the controller terminals - verify continuity
    Repair or replace damaged wiring between sensor and controller
  2. Step 2: Measure S3 sensor resistance at room temperature - NTC type should read approximately 10k ohm at 25C
    Replace sensor if resistance is out of specification
  3. Step 3: Inspect terminal block for corrosion, moisture, or loose connections
    Clean terminals and apply dielectric grease
  4. Step 4: Verify sensor is properly positioned in the evaporator coil sensor well
    Reinsert sensor to proper depth and secure

How to Reset

To reset E1: 1) Press any key on the controller. 2) The alarm will clear if the sensor is now reading correctly. 3) The controller resumes normal operation with S3-based defrost termination.

Common Replacement Parts

  • 084G4000: Danfoss EKC 202C temperature sensor NTC 10k, 3m cable (Verify sensor type matches controller setting)
  • 084G4002: Replacement terminal block for EKC series (Use only Danfoss-approved replacement parts)

Frequently Asked Questions

  • Q: How do I know if the S3 sensor is faulty?

    Measure the resistance across the sensor terminals. At 25C (77F), a good NTC 10k sensor should read approximately 10,000 ohms. An open circuit (infinite resistance) or short circuit (near 0 ohm) indicates a failed sensor.

  • Q: Can the system run without the S3 sensor?

    The system can operate temporarily with time-based defrost only, but this is less efficient and may cause coil icing. Replace the sensor as soon as possible.

Source: Danfoss EKC 202C Controller Technical Guide, Form 202C-TG