Emerson Unidrive SP Error Code O.ht1

Emerson PLC & VFD Major Drive

Model: Unidrive SP | Code: O.ht1

Applicable Systems
Unidrive SP Commander SK EV2000 Mentor MP

Symptoms

The drive trips and displays O.ht1, indicating power module overheat. The thermal sensor on the power module heatsink has detected that the temperature has exceeded the trip threshold, causing the drive to shut down to protect the IGBT modules.

Possible Causes

  • Ambient temperature inside the enclosure exceeds the rated 40-50C
  • Cooling fan stopped or running at reduced speed due to failure
  • Heatsink fins blocked by dust or debris
  • Drive operating at sustained high current near its rated limit

Troubleshooting Steps

  1. Step 1: Check the ambient temperature inside the electrical enclosure
    Temperature should be below 45C; if above, improve ventilation or install cooling
  2. Step 2: Verify the cooling fan is running at full speed
    Fan should spin freely without noise; replace if seized or noisy
  3. Step 3: Clean the heatsink fins using compressed air
    Fins should be clear of dust; verify airflow passage with a light test
  4. Step 4: Measure the drive output current during operation
    If current is consistently above 90% of rated, consider a larger drive or reduce the load

How to Reset

To reset: 1) Allow the drive to cool for at least 10 minutes. 2) Fix the cooling issue. 3) Press RESET. 4) Restart. Caution: Do not immediately reset without allowing the heatsink to cool; the IGBT junction temperature may still be high.

Common Replacement Parts

  • CT-FAN-SP5: Unidrive SP cooling fan assembly (Match to drive frame size; verify airflow direction before installation)

Frequently Asked Questions

  • Q: What temperature triggers O.ht1?

    The power module overheat trip occurs at approximately 90-100C on the heatsink (varies by model). A warning is issued at a lower threshold, giving time to act before a trip.

  • Q: How often should I clean the heatsink?

    Inspect every 6 months in a typical factory environment, or monthly in dusty environments. Clogged heatsinks are the leading cause of overheat trips and premature IGBT failure.

Source: Emerson Control Techniques Unidrive SP Advanced User Guide, 2023

Category: PLC & VFD