Flame Sensor Fault - No Flame Detected

Goodman HVAC Residential Critical HVAC

Model: Goodman GMVC96 Furnace | Code: Goodman E0

Applicable Systems
GMVC96 Furnace GSX14 Condenser AVPTC Air Handler

Symptoms

Flame sensor not detecting flame during ignition cycle; furnace locks out after multiple attempts; no heat.

Possible Causes

  • Flame sensor contaminated with carbon
  • Flame sensor wire loose or corroded
  • Igniter failing to light burners
  • Gas supply interruption

Troubleshooting Steps

  1. Step 1: Check flame sensor for carbon contamination
    Sensor clean (use sandpaper to clean)
  2. Step 2: Verify flame sensor wire connection
    Wire connected securely
  3. Step 3: Check igniter operation during call for heat
    Igniter glows orange
  4. Step 4: Verify gas supply valve is open
    Gas valve open, supply available
  5. Step 5: Clean flame sensor and retry ignition
    Furnace ignites and runs normally

How to Reset

Clear by cycling furnace power OFF/ON (kill switch or breaker); retry ignition.

Common Replacement Parts

  • Goodman Flame Sensor Kit
  • Hot Surface Igniter

Frequently Asked Questions

  • Q: How to clean flame sensor?

    Remove sensor from burner assembly. Clean metal rod with fine sandpaper or steel wool (not emery cloth). Wipe with clean cloth. Reinstall and test.

Source: Goodman GMVC96 Service Manual

Category: HVAC Residential