Pressure Switch Open - Inducer Running

Goodman HVAC Residential Critical HVAC

Model: Goodman GMVC96 Furnace | Code: Goodman E1

Applicable Systems
GMVC96 Furnace GSX14 Condenser AVPTC Air Handler

Symptoms

Pressure switch did not close after inducer motor starts; furnace will not light; possible vent blockage or inducer failure.

Possible Causes

  • Vent pipe blocked or restricted
  • Pressure switch tubing cracked/loose
  • Inducer motor not reaching full speed
  • Pressure switch faulty

Troubleshooting Steps

  1. Step 1: Check vent pipe for blockage (bird nest, debris)
    Vent clear
  2. Step 2: Inspect pressure switch tubing for cracks/loose fit
    Tubing intact, connections tight
  3. Step 3: Verify inducer motor reaches full speed
    Inducer runs at full speed
  4. Step 4: Test pressure switch with manometer
    Pressure switch closes at correct draft
  5. Step 5: Replace pressure switch if faulty
    Furnace sequence completes

How to Reset

Clear by cycling furnace power; clear any blockage before retry.

Common Replacement Parts

  • Goodman Pressure Switch P/N: B1370735
  • Pressure Switch Tubing

Frequently Asked Questions

  • Q: What does the pressure switch do?

    Confirms adequate draft (negative pressure) from inducer motor before allowing gas valve to open. Safety device preventing gas flow without proper venting.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Goodman GMVC96 Service Manual

Category: HVAC Residential