Applicable Systems
GMVC96 Furnace
GSX14 Condenser
AVPTC Air Handler
Symptoms
Pressure switch did not close after inducer motor starts; furnace will not light; possible vent blockage or inducer failure.
Possible Causes
- Vent pipe blocked or restricted
- Pressure switch tubing cracked/loose
- Inducer motor not reaching full speed
- Pressure switch faulty
Troubleshooting Steps
- Step 1: Check vent pipe for blockage (bird nest, debris)
Vent clear - Step 2: Inspect pressure switch tubing for cracks/loose fit
Tubing intact, connections tight - Step 3: Verify inducer motor reaches full speed
Inducer runs at full speed - Step 4: Test pressure switch with manometer
Pressure switch closes at correct draft - Step 5: Replace pressure switch if faulty
Furnace sequence completes
How to Reset
Clear by cycling furnace power; clear any blockage before retry.
Common Replacement Parts
- Goodman Pressure Switch P/N: B1370735
- Pressure Switch Tubing
Frequently Asked Questions
- Q: What does the pressure switch do?
Confirms adequate draft (negative pressure) from inducer motor before allowing gas valve to open. Safety device preventing gas flow without proper venting.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Goodman GMVC96 Service Manual
Category: HVAC Residential