Pressure Switch Open - Inducer Running

Goodman HVAC Residential Critical HVAC

Model: Goodman GMVC96 Furnace | Code: Goodman E1

Applicable Systems
GMVC96 Furnace GSX14 Condenser AVPTC Air Handler

Symptoms

Pressure switch did not close after inducer motor starts; furnace will not light; possible vent blockage or inducer failure.

Possible Causes

  • Vent pipe blocked or restricted
  • Pressure switch tubing cracked/loose
  • Inducer motor not reaching full speed
  • Pressure switch faulty

Troubleshooting Steps

  1. Step 1: Check vent pipe for blockage (bird nest, debris)
    Vent clear
  2. Step 2: Inspect pressure switch tubing for cracks/loose fit
    Tubing intact, connections tight
  3. Step 3: Verify inducer motor reaches full speed
    Inducer runs at full speed
  4. Step 4: Test pressure switch with manometer
    Pressure switch closes at correct draft
  5. Step 5: Replace pressure switch if faulty
    Furnace sequence completes

How to Reset

Clear by cycling furnace power; clear any blockage before retry.

Common Replacement Parts

  • Goodman Pressure Switch P/N: B1370735
  • Pressure Switch Tubing

Frequently Asked Questions

  • Q: What does the pressure switch do?

    Confirms adequate draft (negative pressure) from inducer motor before allowing gas valve to open. Safety device preventing gas flow without proper venting.

Source: Goodman GMVC96 Service Manual