Hitachi WJ200 Error Code E26

Hitachi PLC & VFD Major Motor

Model: WJ200 | Code: E26

Applicable Systems
WJ200

Symptoms

The WJ200 reports an auto-tune failure. The automatic motor parameter measurement did not complete successfully.

Possible Causes

  • Motor not connected or connected incorrectly during auto-tune
  • Motor load present during auto-tune preventing accurate measurement
  • Motor parameters entered are too far from actual values for convergence

Troubleshooting Steps

  1. Step 1: Verify the motor is connected and wiring is correct in the drive
    Motor is properly connected
  2. Step 2: Remove any load from the motor before running auto-tune
    Motor shaft is free to rotate without load
  3. Step 3: Enter the motor nameplate parameters before running auto-tune
    Parameters are entered and auto-tune converges

How to Reset

To reset: Correct the motor connection and load, then retry auto-tune.

Source: Hitachi WJ200 Inverter Manual, Hitachi Industrial Equipment

Category: PLC & VFD