Hitachi WJ200 Error Code E35

Hitachi PLC & VFD Major Overcurrent

Model: WJ200 | Code: E35

Applicable Systems
WJ200

Symptoms

The WJ200 reports an overcurrent fault detected at the output. The drive trips to protect the power semiconductor devices.

Possible Causes

  • Motor cable short circuit or ground fault in the Hitachi output wiring
  • Motor winding insulation failure causing excessive current
  • Accelerated too rapidly causing inrush current beyond the drive capacity

Troubleshooting Steps

  1. Step 1: Inspect the motor cable and motor windings for short circuits or ground faults with a megger
    Insulation resistance is above the minimum threshold
  2. Step 2: Reduce the acceleration time parameter to limit inrush current
    Peak current stays within the drive rated value
  3. Step 3: If the motor is defective, repair or replace the motor
    New motor draws current within rated range

How to Reset

To reset: Resolve the overcurrent root cause, then reset the fault via the keypad or cycle power.

Source: Hitachi WJ200 Inverter Manual, Hitachi Industrial Equipment

Category: PLC & VFD