Mitsubishi FR-A800 Error Code E.THM

Mitsubishi PLC & VFD Major Motor

Model: FR-A800 | Code: E.THM

Applicable Systems
MELSEC FX3U MELSEC FX5U FR-A800 FR-A700 MR-J4 iQ-R Motion Controller (R32MTCPU/R16MTCPU)

Symptoms

The drive trips and the panel displays E.THM, indicating motor thermal overload. The electronic thermal relay function has detected that the motor current has exceeded the thermal protection threshold for a sustained period.

Possible Causes

  • Actual motor overload due to excessive mechanical load
  • Motor cooling fan or ventilation blocked causing thermal buildup
  • Electronic thermal relay parameter (Pr.9) set too low for the motor rating
  • Motor rated current parameter mismatch causing false overload detection

Troubleshooting Steps

  1. Step 1: Measure the actual motor current during operation
    Current should be at or below the motor rated current; if above, reduce the load
  2. Step 2: Inspect the motor cooling fan and ventilation paths
    Fan should spin freely; air passages should be clear of dust and debris
  3. Step 3: Verify parameter Pr.9 (electronic thermal relay) matches the motor rated current
    Pr.9 should equal the motor nameplate rated current
  4. Step 4: Check if the motor duty cycle is within the rated S1 (continuous) or S3 (intermittent) specification
    If intermittent duty, ensure the on/off ratio is within the motor thermal capacity

How to Reset

To reset: 1) Press STOP/RESET. 2) Reduce the load or fix the cooling. 3) Verify Pr.9 setting. 4) Restart. Caution: Running a motor in an overloaded condition can cause insulation failure and permanent damage.

Frequently Asked Questions

  • Q: How does the electronic thermal relay work without a physical sensor?

    The drive calculates motor heating based on the measured current and the thermal time constant. It simulates the motor's thermal state using the current level and duration. For accurate protection, Pr.9 must match the motor rated current.

  • Q: Can I disable the electronic thermal relay?

    Yes, set Pr.9 to 0. However, this is strongly discouraged as it removes motor thermal protection. Use an external thermal sensor (PTC/PT100) instead if the built-in function is not suitable.