NORD SK Error Code N029

NORD PLC & VFD Critical Inverter

Model: SK | Code: N029

Applicable Systems
SK

Symptoms

The SK reports an inverter stage fault. The output inverter section detected a fault in the IGBT power switching circuit.

Possible Causes

  • IGBT module failure or degradation
  • Gate drive circuit fault preventing proper IGBT switching
  • DC bus capacitor degradation causing excessive ripple current

Troubleshooting Steps

  1. Step 1: Check the IGBT module for short circuit between collector and emitter
    IGBT shows no short circuit
  2. Step 2: Verify the gate drive signal with an oscilloscope
    Gate drive signal has correct amplitude and timing
  3. Step 3: If the IGBT is faulty, replace the drive unit
    New unit operates with healthy IGBT modules

How to Reset

To reset: Fix the inverter fault or replace the unit, then restart.

Source: NORD SK Drive System Manual, NORD Drives

Category: PLC & VFD