Applicable Systems
EFC
FEX
FEI
HNC
Symptoms
PWM timer synchronization fault. The drive has detected a synchronization error in the PWM (Pulse Width Modulation) timer that controls IGBT switching.
Possible Causes
- Control board FPGA timing error
- PWM carrier frequency set too high for the hardware
- Interference from another drive on the same power supply
- Firmware version incompatibility with PWM timer hardware
Troubleshooting Steps
- Step 1: Check PWM carrier frequency setting in IndraWorks AS
Frequency within the rated range for the drive model (typically 2-16 kHz) - Step 2: Verify no other drives on the same power supply are causing synchronization issues
Each drive operates independently without interference - Step 3: Power-cycle the drive to reset the PWM timer
Timer synchronizes correctly after restart - Step 4: If fault recurs, reload firmware or replace control module
New control module provides stable PWM timing
How to Reset
1) Check PWM frequency parameter. 2) Power-cycle. 3) Reload firmware. 4) Replace control module if persistent.
Frequently Asked Questions
- Q: What PWM carrier frequency should I use?
Default is typically 4-8 kHz. Higher frequencies reduce motor noise but increase drive heating. Consult the motor and drive specifications.
- Q: Does PWM timer fault affect motor performance?
Yes. PWM timing errors can cause uneven motor torque, increased ripple, and potential motor heating. Address immediately.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Rexroth IndraDrive HCS/HMS Fault Code List, Bosch Rexroth AG