Rexroth IndraDrive HCS Error Code F8122

Rexroth PLC & VFD Critical Hardware

Model: IndraDrive HCS | Code: F8122

Applicable Systems
EFC FEX FEI HNC

Symptoms

Control component damaged. The drive has detected a hardware defect in the control module that prevents safe operation. The drive cannot be started.

Possible Causes

  • Control board CPU or FPGA failure
  • Control board power supply component failure
  • Physical damage from impact or liquid ingress
  • Electrostatic discharge (ESD) damage to control board components

Troubleshooting Steps

  1. Step 1: Inspect control board visually for physical damage, burn marks, or corrosion
    No visible damage; if damage is present, board must be replaced
  2. Step 2: Check for environmental factors: moisture, dust, or chemical contamination
    Control cabinet is clean and dry; no signs of contamination
  3. Step 3: Verify all ground connections to prevent ESD events
    All grounds properly bonded; no floating grounds
  4. Step 4: Replace control module
    New module initializes and operates correctly

How to Reset

1) Visual inspection of control board. 2) Check environmental conditions. 3) Verify grounding. 4) Replace control module. Caution: Do not attempt PCB-level repair of control components.

Common Replacement Parts

  • R911319000: IndraDrive control module (Verify exact part number by drive model)

Frequently Asked Questions

  • Q: What causes control component damage?

    Most commonly: ESD events, voltage transients, overheating, or physical impact. Proper grounding and environmental control prevent most cases.

  • Q: Can the control board be repaired?

    No. Control board repair requires factory-level equipment. Field replacement of the complete control module is the standard procedure.

Comments (0)