Rexroth IndraDrive HCS Error Code F8813

Rexroth PLC & VFD Major Hardware

Model: IndraDrive HCS | Code: F8813

Applicable Systems
EFC FEX FEI HNC

Symptoms

Power choke connection fault. The drive has detected a problem with the power choke (DC link reactor) connection. Current ripple may increase, stressing DC link capacitors.

Possible Causes

  • Power choke wiring loose or disconnected
  • Power choke winding open circuit
  • Choke temperature sensor (if equipped) indicating overtemperature
  • Choke terminal corrosion causing high resistance

Troubleshooting Steps

  1. Step 1: Inspect power choke connections at drive terminals
    All connections torqued to specification; no loose terminals
  2. Step 2: Measure choke winding resistance
    Winding resistance within specification; no open circuit
  3. Step 3: Check choke temperature (if temperature sensor equipped)
    Temperature within rated range; no overheating indication
  4. Step 4: Replace power choke if winding is open or temperature is abnormal
    New choke connects without fault

How to Reset

1) Power off. 2) Inspect choke connections. 3) Measure winding. 4) Replace if defective. 5) Reset fault.

Frequently Asked Questions

  • Q: What does the power choke do?

    The DC link power choke reduces current ripple in the DC bus, protecting capacitors and improving power factor. It is standard on larger drive models.

  • Q: Can I run without the power choke?

    No. The power choke is essential for proper DC link operation. Running without it will cause excessive current ripple and premature capacitor failure.

Source: Rexroth IndraDrive HCS/HMS Fault Code List, Bosch Rexroth AG

Category: PLC & VFD