Applicable Systems
RA17 Condenser
R96V Furnace
RA14 Condenser
Symptoms
Outdoor fan motor not running; condenser cannot reject heat; compressor will trip on high pressure if not protected.
Possible Causes
- Fan motor run capacitor failed
- Fan motor bearings seized
- Fan motor wiring damaged
- Contactor not sending power to fan
Troubleshooting Steps
- Step 1: Check fan motor run capacitor (5-15 MFD typical)
Capacitance within +/- 5% of rating - Step 2: Try spinning fan blade by hand (power off) - check for seized bearings
Blade spins freely - Step 3: Check power at fan motor contactor
240V present at contactor - Step 4: Replace capacitor or fan motor as needed
Fan motor runs at full speed - Step 5: Verify condenser airflow is adequate
Airflow strong and steady
How to Reset
Clear by cycling power after fan motor service.
Common Replacement Parts
- Rheem Outdoor Fan Motor
- Dual Run Capacitor
Frequently Asked Questions
- Q: How to test fan motor capacitor?
Use multimeter with capacitance function. Discharge capacitor first (short terminals). Reading should be within +/- 5% of rating printed on capacitor.
Source: Rheem RA17 Service Manual