Applicable Systems
ATV320
ATV340
ATV630
ATV930
Symptoms
The drive has detected a short circuit between output phases or between an output phase and ground. This is a critical fault that requires immediate attention.
Possible Causes
- Short circuit between motor output phases (T1-T2, T2-T3, T1-T3)
- Short circuit between motor output and ground
- Motor winding insulation failure
- Motor cable damaged and shorting
Troubleshooting Steps
- Step 1: Disconnect the motor cables from the drive output terminals
Cables are safely disconnected - Step 2: Measure resistance between all motor phases and between each phase and ground
No short circuits detected - all resistances are within motor specifications - Step 3: Inspect motor cable insulation along the entire length
Cable insulation is intact with no damage - Step 4: If motor and cables are OK, the drive output stage may be damaged - contact Schneider service
Drive is tested and repaired if needed
How to Reset
To reset: 1) Disconnect motor and check for shorts. 2) Repair any short circuit found. 3) Press STOP/RESET. 4) Restart. Do NOT reset without fixing the short - drive damage may result.
Source: Schneider ATV320 Programming Manual
Category: Electrical