Applicable Systems
S7-1200
S7-1500
S7-300
S7-400
LOGO!
SINAMICS
Symptoms
DC link overvoltage: regenerative energy exceeds limit.
Possible Causes
- Deceleration time too short
- No brake chopper connected
- Mains voltage too high
Troubleshooting Steps
- Step 1: Increase ramp-down time
No overvoltage trip - Step 2: Connect brake chopper and resistor
DC link voltage controlled - Step 3: Check mains supply voltage
Voltage within rated range
How to Reset
Reset via operator panel after resolving overvoltage.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Siemens SINAMICS G120 List Manual
Category: PLC & VFD
Published: 2026-10-08
No comments yet. Be the first to share your experience!