Siemens SINAMICS V90 Error Code F1910

Siemens PLC & VFD Major Communication

Model: SINAMICS V90 | Code: F1910

Applicable Systems
S7-1200 S7-1500 S7-300 S7-400 LOGO! SINAMICS

Symptoms

Fieldbus setpoint reception interrupted. The V90 has stopped receiving setpoint data from the fieldbus (PROFINET or PROFIdrive). The motor is stopped using the configured bus fault reaction.

Possible Causes

  • PROFINET cable disconnected or damaged
  • PROFINET switch failure
  • PLC (PROFINET controller) stopped or crashed
  • Communication parameters mismatch between PLC and V90

Troubleshooting Steps

  1. Step 1: Check PROFINET cable connection at V90 and switch/controller
    Cable fully inserted; link LEDs on both ends lit
  2. Step 2: Verify PROFINET switch is powered and operational
    Switch is running; all port LEDs normal
  3. Step 3: Check PLC status: is it in RUN mode and sending setpoints?
    PLC is in RUN; no diagnostic errors
  4. Step 4: Verify PROFINET device name and IP address match the PLC configuration
    Device name and IP match; no addressing conflict

How to Reset

1) Check cable. 2) Verify switch. 3) Check PLC status. 4) Verify device name/IP. 5) Reset fault.

Frequently Asked Questions

  • Q: What is the bus fault reaction for V90?

    Configurable options: STO (Safe Torque Off - immediate), Stop with ramp (controlled deceleration), or Hold last setpoint (maintain speed). Configured via parameter p1250.

  • Q: How do I configure the PROFINET device name?

    In Siemens TIA Portal hardware configuration, set the device name. Then use the 'Accessible Devices' dialog to download the name to the V90 via PROFINET.

Source: Siemens SINAMICS V90 Operating Instructions, Edition 01/2023

Category: PLC & VFD