Applicable Systems
S7-1200
S7-1500
S7-300
S7-400
LOGO!
SINAMICS
Symptoms
Encoder ground fault: encoder circuit leakage to ground.
Possible Causes
- Encoder cable insulation breakdown
- Encoder internal ground fault
- Wiring fault
Troubleshooting Steps
- Step 1: Megger test encoder cable to ground
Insulation > 1 MOhm - Step 2: Inspect encoder wiring
No ground fault path - Step 3: Replace encoder if internal fault
New encoder operates correctly
How to Reset
Reset via operator panel after encoder ground fault is repaired.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Siemens SINAMICS G120 List Manual
Category: PLC & VFD
No comments yet. Be the first to share your experience!