Applicable Systems
Vitodens

Symptoms

The boiler fails to ignite after three consecutive attempts. The flame detection circuit does not confirm a flame and the controller enters a lockout state.

Possible Causes

  • Ignition electrode gap too wide or fouled with carbon buildup
  • Gas valve not opening or gas pressure below the minimum required for ignition
  • Flame sensor rod contaminated or cracked, failing to detect the flame
  • Ignition transformer failed, not producing the high-voltage spark

Troubleshooting Steps

  1. Step 1: Inspect and clean the ignition electrode and flame sensor rod
    Electrode gap should be 3-5mm; clean with emery cloth
  2. Step 2: Check the gas inlet pressure at the test port with a manometer
    Natural gas should read 7-11 inches water column at the inlet
  3. Step 3: Test the ignition transformer by measuring spark output with a spark tester
    A strong blue spark should jump the gap; replace if weak or absent
  4. Step 4: Verify the gas valve opens by listening for the click during the ignition sequence
    If silent, test the valve coil resistance and control voltage

How to Reset

Reset: Press and hold the reset button on the boiler controller for 3 seconds. If lockout recurs, do not attempt further resets - call a qualified technician.

Common Replacement Parts

  • Ignition electrode: OEM-specified, includes ceramic (Match to boiler model)
  • Flame sensor rod: Single-rod or dual-rod type (Clean with emery cloth, not sandpaper)
  • Ignition transformer: 120V primary, 10kV secondary (Match to boiler model)

Frequently Asked Questions

  • Q: How many times can I press reset?

    Maximum 3 times within 10 minutes. Repeated lockouts indicate a serious fault requiring professional service.

  • Q: What gas pressure do I need?

    Natural gas: 7-11 inches WC inlet. Propane: 11-13 inches WC. Verify with a manometer before adjustment.

  • Q: How often should I service the ignition?

    Annually before heating season. Clean electrodes, check gas pressure, and verify flame signal strength (minimum 2 microamps DC).

Source: OEM Installation Manual

Category: Home Boiler