ABB MNS-MCC Error Code E-102

ABB Electrical Critical Ground Fault

Model: MNS-MCC | Code: E-102

Applicable Systems
MNS-MCC

Symptoms

The earth-fault relay trips and the main incomer breaker opens. The fault log displays G/F and the magnitude is recorded as >30% of rated current. The green Healthy LED extinguishes.

Possible Causes

  • Insulation breakdown in motor windings or cable insulation
  • Moisture ingress into cable glands or terminal boxes
  • Damage to cable sheath causing phase-to-ground contact
  • Incorrect grounding of MCC enclosure creating stray currents

Troubleshooting Steps

  1. Step 1: Isolate the affected motor feeder and megger the motor windings to ground
    Insulation resistance reads >10 MOhm at 500V DC
  2. Step 2: Inspect all cable entry glands and terminal box seals for water ingress
    Glands are dry, seals intact, and drain holes are unobstructed
  3. Step 3: Perform a step-voltage insulation test on the power cables from breaker to motor
    No breakdown occurs up to 2kV DC and leakage current is stable
  4. Step 4: Verify the MCC ground bus is bonded to the building ground electrode with a low-impedance path
    Ground impedance is <1 Ohm per IEEE 142

How to Reset

Reset the earth-fault relay by pressing the reset pushbutton after isolating and rectifying the ground fault. Reclose the incomer only after confirming zero residual ground current on the relay display.

Common Replacement Parts

  • 1SFA897502R1000: ABB REJ603 earth-fault relay (Compatible with MNS 2.0 and MNS 3.0 platforms)

Frequently Asked Questions

  • Q: How sensitive should the earth-fault setting be?

    For motor feeders, a typical setting is 30% of FLA with a 0.1-0.3s delay to allow for motor starting transients.

  • Q: What if the fault clears when I disconnect the motor?

    This indicates the fault is likely in the motor windings or the cable segment between the breaker and the motor. Megger each component separately.

Source: ABB MNS-MCC Technical Manual, Edition 04/2022