ABB MNS-MCC Error Code E-110

ABB Electrical Major Protection

Model: MNS-MCC | Code: E-110

Applicable Systems
MNS-MCC

Symptoms

The arc flash detection system has activated. The main breaker tripped within 2ms of detecting an arc flash event, preventing catastrophic equipment damage.

Possible Causes

  • Arc flash caused by insulation failure between phase busbars
  • Foreign object or tool left inside the switchgear creating a phase-to-phase short
  • Condensation or water ingress in the switchgear causing tracking and flashover
  • Loose busbar connection creating an arc under load current

Troubleshooting Steps

  1. Step 1: Do NOT approach the switchgear until the arc flash energy has dissipated and the area is verified safe
    Wait at least 5 minutes after trip for any secondary arcs or fires to self-extinguish
  2. Step 2: Open the switchgear door and visually inspect for arc damage, soot, or molten metal
    Photograph the damage for insurance and investigation records
  3. Step 3: Use a megohmmeter to test all busbar insulation to ground and phase-to-phase
    Insulation resistance should be above 100 megohms; if below, the busbar needs cleaning or replacement
  4. Step 4: Tighten all busbar connections to the manufacturer's torque specification
    Use a calibrated torque wrench; replace any hardware showing signs of overheating

How to Reset

Reset: The arc flash relay requires a manual reset with a key switch after the root cause is identified and corrected. This prevents reset without proper investigation.

Common Replacement Parts

  • Arc flash relay: High-speed, 2ms trip time (Light and current sensing for arc detection)
  • Busbar insulation: Epoxy or polyester film (Replace if tracking or carbonization is visible)
  • Phase barrier: Glass-polyester sheet, 3mm (Replace any barrier showing arc damage)

Frequently Asked Questions

  • Q: What is an arc flash?

    An electrical explosion caused by a phase-to-phase or phase-to-ground fault, releasing intense heat, light, and pressure energy.

  • Q: How do I prevent arc flash?

    Maintain insulation integrity, keep the switchgear clean and dry, torque all connections properly, and use arc-rated PPE when working on energized equipment.

  • Q: What PPE is required for switchgear work?

    Category 4 PPE for line-side work: 40 cal/cm2 arc-rated suit, face shield, and insulated gloves. Follow NFPA 70E or local standards.

Source: OEM Technical Manual